Power Supply
Last modified: 10 July 2022, 10:42:24 AM AEST
Types1 / 9
- RCD 3 = Red power points
- Essential Power
- Backed up with generator power
- RCD 2 = Blue power points
- UPS = Uninterruptible Power Supply
- 1 UPS per OT
- Battery backup for 30 minutes
- And generator backup
- White power points
- Grid only, no backup
- Specialty power supply
- 1 x 32 A 3-phase outlet
- More power
- for lasers
- 1 per OT
Powerpoints2 / 9
- 10 A = normal
- 15 A = taller vertical slot = for heaters / coolers / CPB
RCD = Residual Current Device3 / 9
- safety device
- components
- power source
- active wire
- neutral wire
- detector coil = around both wires = no current flow
- switches off electricity automatically if there is fault
- detects if the current flow through the active and neutral wires is equal
- if fault results in current leaking to earth, then flow will be different
- current will be induced in detector coil
- circuit breakers are tripped and power supply is stopped
- will detect current leak 5-10 mA
- will "trip" within 10-20 ms = protect against macroshock
- does NOT protect against
- current going through body and back via neutral (rare)
- microshocks
- power points protected by an RCD are RED
- Types
- Non-portable = fixed socket outlet on wall
- Portable = incorporated into power cables or power boards
LIM = Line Isolation Monitor4 / 9
- components
- primary circuit
- secondary circuit
- line isolation monitor = detects difference in current in both circuits
- LIM will alarm if prospective hazard current > 5 mA
- difference between RCD and LIM
- RCD will interrupt power
- LIM will alarm but will NOT interrupt supply
- This is so that power to critical life support equipment is not shut off
- if the LIM alarms, you should unplug that last item of equipment that was plugged in
- that is the most likely source of the fault
- LIM alarm
- check gauge
- threshold = 2 mA
- 2-5 mA = likely too much electrical equipment plugged in
- 5+ mA = likely faulty piece of equipment
- Power points protected by a LIM are BLUE
Equipotential Earthing System = EES5 / 9
- Normal for earth wires at different power points to have a small potential difference
- due to different sum of resistances in the wires and connections
- EES uses a large diameter copper cable to connect all earth points in a room together
- Reduces the potential sources of a microshock
- EES is requirement for a cardiac protected treatment area
- These are the green knobs = "EP Junction" with a test green knob
Power-critical devices6 / 9
- Cardiac bypass machines
- have a hand crank as back up
- Ventilators
- Some have no battery backup
- Anaesthetic machines
- 90 minutes of battery backup
Applied Parts7 / 9
- Unprotected
- Type B = Unprotected
- Symbol = Man
- Some equipment cannot be constucted
- Body Protected
- Type BF = Body Protected / Floating
- Symbol = Man in a box
- Cardiac Protected
- Type CF = Cardiac Protected, Floating
- Current is limited to prevent microshock
- max allowable leakage
- Class I = 50 uA
- Class II = 10 uA
- max allowable leakage
- Symbol = heart in box
Treatment Areas8 / 9
- Body Protected Treatment Area
- RCD / LIM
- Protection from macroshock
- Cardiac Protected Treatment Area
- Required where direct cardiac connection is likely
- Offers protection from microshock
- Requires RCD / LIM
- Also requires equipotential earthing system
- This means PICCs should not be inserted in ward, unless in cardiac protected treatment room
References9 / 9
https://www.mak95.com/studynotes/Equipment%20Safety.html
https://litfl.com/prevention-of-electrocution/
https://www.adelaide.edu.au/hr/ua/media/6261/rcds-appendix-c.pdf
https://propofoldreams.files.wordpress.com/2015/03/physics-electrical-safety.pdf
https://aneskey.com/electrical-and-fire-safety-3/
https://www.apsf.org/article/line-isolation-still-important/